Overview KOM300F is an industrial fiber optic converter which can work in harsh electromagnetic environment and wide range of temperature.
Key Features 1. 2 10/100Base-TX ports and 1 100Base-FX port 2. EMC performance reaches industrial level 4 3. IP40 protection class 4. CE, FCC certificates
Standard IEEE 802.3i IEEE 802.3u
Switch Properties MAC Table: 2K Packet Buffer: 1Mbit Packet Forwarding Rate: 0.8Mpps Switching Delay: <5μs
Interface Fast Ethernet Fiber Ports: 1 100Base-FX, SM/MM port, FC/SC/ST connector Fast Ethernet RJ45 Ports: 2 10/100Base-TX RJ45 ports
LED LEDs on Front Panel: Running LED: Run Power LED: PWR1, PWR2 Interface LED: Link/ACT, Speed (RJ45 port)
Transmission Distance Twisted Pair: 100m (Standard CAT5, CAT5e network cable) Multi Mode Fiber: 1310nm, 5km (100M) Single Mode Fiber: 1310nm, 40km/60km (100M) 1550nm, 60km/80km (100M)
Power Requirements Power Input: 24VDC (9-36VDC), 48VDC (36-72VDC), 110VDC (70-140VDC), 220VAC/DC (85-264VAC/120-370VDC) Power Terminal: 3-pin 3.81mm-sapcing plug-in terminal block Power Consumption: <4.1W
Overload Protection: Support Reverse Connection Protection: Support |
|
Physical Characteristics Housing: Metal, fanless Protection Class: IP40 Dimensions (W×H×D): 36×100×75mm (1.42×3.94×2.95 in.) Weight: 0.3kg (0.661 pound) Mounting: DIN-Rail or Panel mounting
Environmental Limits Operating Temperature: -40 to 85°C (-40 to 185°F) Storage Temperature: -40 to 85°C (-40 to 185°F) Ambient Relative Humidity: 5 to 95% (non-condensing)
MTBF 462,741 hrs
Warranty 5 years
Approvals CE, FCC
Industrial Standard EMI: FCC CFR47 Part 15, EN55022/CISPR22, Class A
EMS: IEC61000-4-2 (ESD): ±8kV (contact), ±15kV (air) IEC61000-4-3 (RS): 10V/m (80MHz-2GHz) IEC61000-4-4 (EFT): Power Port: ±4kV; Data Port: ±2kV IEC61000-4-5 (Surge): Power Port: ±2kV/DM, ±4kV/CM; Data Port: ±2kV IEC61000-4-6 (CS): 3V (10kHz-150kHz); 10V (150kHz-80MHz) IEC61000-4-16 (Common mode conduction): 30V (cont.), 300V (1s)
Machinery: IEC60068-2-6 (Vibration) IEC60068-2-27 (Shock) IEC60068-2-32 (Free Fall)
Industry: IEC61000-6-2 Railway: EN50155, EN50121-4 |